Primary and Secondary Windings:
The CT consists of a primary winding (few turns, connected in series with the high-current circuit) and a secondary winding (many turns, connected to low-power devices like meters or relays).
When an AC current flows through the primary winding, it generates a time-varying magnetic flux in the core, inducing a proportional current in the secondary winding.
Current Ratio:
The ratio of primary current (I1) to secondary current (I2) is inversely proportional to the turns ratio (N1/N2):I2I1=N1N2orI1=I2×N1N2
Example: A CT with a turns ratio of 1:100 (1 primary turn, 100 secondary turns) will reduce a 500A primary current to 5A on the secondary side (500A=5A×100).
Core Material:
Typically made of silicon steel (for low losses at power frequencies, 50/60 Hz) or ferrite (for high-frequency applications, up to 100kHz).
Burden (Load):
The secondary circuit’s impedance must not exceed the CT’s rated burden (in VA) to avoid core saturation and measurement errors.
Accuracy Class:
Defines the maximum allowable error in current transformation (e.g., Class 0.5 allows ±0.5% error at rated current).
Type | Description | Applications |
---|---|---|
Bar-Type (Through-Type) | No visible primary winding; the conductor itself passes through the CT core. | Low-voltage (LV) and medium-voltage (MV) systems (e.g., 400V switchgear). |
Wound-Type | Primary winding is integrated into the CT (e.g., 10–20 turns for high currents). | High-voltage (HV) systems (e.g., 11kV, 33kV substations). |
Split-Core (Clamp-On) | Core can be opened to clamp around a live conductor without disconnecting it. | Retrofitting or temporary measurements (e.g., in industrial maintenance). |
Toroidal | Circular core with secondary winding evenly distributed around the primary conductor. | High-accuracy metering and low-leakage applications. |
Low-Voltage (LV) CTs:
Rated for primary voltages ≤ 1 kV.
Example: 500A/5A CTs in LV distribution panels.
High-Voltage (HV) CTs:
Rated for primary voltages ≥ 1 kV.
Use oil-immersed or gas-insulated designs for dielectric strength (e.g., 110kV CTs in transmission grids).
Metering CTs:
High accuracy (Class 0.2 or 0.5) for energy billing and power quality analysis.
Example: CTs in smart meters for residential solar systems.
Protection CTs:
Prioritize reliability during faults (e.g., Class 5P20, which allows 5% error at 20x rated current).
Used in protective relays to detect overcurrent or short circuits.
Special-Purpose CTs:
Rogowski Coils: High-frequency CTs for pulse or harmonic-rich signals (e.g., in variable frequency drives).
Hall Effect CTs: Non-contact, solid-state sensors for DC or AC measurement (used in EV charging systems).
Optical CTs: Use fiber optics for immunity to electromagnetic interference (EMI), ideal for HV and digital substations.
Iron Core CTs:
Traditional silicon steel cores for most power system applications.
Air Core CTs:
No magnetic core; used for very high currents or wide frequency ranges (e.g., in arc furnaces).
Energy Metering:
Measure active and reactive power in residential, commercial, and industrial settings.
Example: A 200A/5A CT in a factory’s main distribution board for billing purposes.
Protective Relaying:
Detect abnormal currents (e.g., short circuits) and trigger circuit breakers.
Example: A 1000A/1A protection CT in a 33kV substation’s feeder line.
Power Quality Monitoring:
Analyze harmonic content, unbalanced currents, and load profiles.
Example: CTs in a data center’s UPS system to monitor THD (total harmonic distortion).
Renewable Energy Systems:
Monitor inverter output in solar/wind farms (e.g., 690V/5A CTs in wind turbine nacelles).
Industrial Automation:
Provide current feedback to variable frequency drives (VFDs) and motor control systems.
Polarity:
CTs have a polarity marking (e.g., “*” or “H1/X1”) to ensure correct phase relationship between primary and secondary currents.
Burden Calculation:
The secondary burden (Zburden) must satisfy:Zburden≤Secondary Current2Rated VA
Example: A 5A CT with a 25VA burden can tolerate a maximum load impedance of 25VA/(5A)2=1Ω.
Saturation Limits:
CTs must avoid saturation under fault conditions (e.g., 20x rated current for protection CTs).
IEC 60044-1: General requirements for instrument transformers (CTs).
ANSI C57.13: U.S. standard for CT accuracy, testing, and safety.
GB/T 1208: Chinese national standard for current transformers.
IEEE C37.110: Guidelines for CT applications in protective relaying.
Core Saturation:
Cause: Excessive primary current or high secondary burden.
Solution: Use larger cores, lower burden instruments, or saturable cores for protection CTs.
EMI Interference:
Cause: Proximity to high-voltage lines or motors.
Solution: Shield secondary cables with copper foil and use twisted-pair wiring.
Temperature Effects:
Cause: High ambient temperature affecting core losses.
Solution: Use high-temperature insulation (e.g., Class H) and improve ventilation.
Digital CTs (DCTs):
Convert analog current signals to digital outputs (e.g., IEC 61850-compatible) for smart grid integration.
Optical and Fiber-Optic CTs:
Offer immunity to EMI and high-voltage isolation, suitable for UHV (ultra-high voltage) systems.
IoT and AI Integration:
Smart CTs with built-in sensors for real-time health monitoring and predictive maintenance.
Eco-Friendly Designs:
Use biodegradable insulation and recyclable core materials (e.g., amorphous metal for low losses).
I graduated from the University of Electronic Science and Technology, majoring in electric power engineering, proficient in high-voltage and low-voltage power transmission and transformation, smart grid and new energy grid-connected technology applications. With twenty years of experience in the electric power industry, I have rich experience in electric power design and construction inspection, and welcome technical discussions.