Ensure Selective Fault Isolation: CTs must accurately measure fault currents to enable relays to trip only the faulty circuit.
Guarantee Protection Sensitivity: CTs should provide sufficient current transformation ratio (CT ratio) to detect low-magnitude faults.
Maintain Protection Speed and Reliability: Proper CT placement and rating minimize protection misoperation or refusal.
Protection Function | CT Placement Requirement | Rationale |
---|
Line Protection | At both ends of transmission lines (breaker sides). | Enables differential protection to compare currents at line terminals for rapid fault identification. |
Transformer Protection | On each winding side (high-voltage, medium-voltage, low-voltage). | Facilitates differential protection against internal faults and backup protection for external faults. |
Busbar Protection | At each bus section and incoming/outgoing feeder connections. | Enables busbar differential protection to isolate faults within the bus zone. |
Generator Protection | Near the generator terminals and neutral grounding points. | Monitors stator and rotor currents for overcurrent, differential, and ground fault protection. |
Polarity Consistency:
CTs in differential protection systems (e.g., transformer or busbar differential) must have consistent polarity to avoid false differential currents.
Polarity marking (e.g., P1 to S1) must align with relay requirements to ensure correct phase comparison.
Wiring Configurations:
Star (Y) Connection: Used for phase and ground fault protection, providing a neutral point for ground current measurement.
Delta (Δ) Connection: Mitigates zero-sequence currents in transformer differential protection or voltage compensation.
Series/Parallel Connections: Adjust secondary current for relay input compatibility (e.g., 1 A or 5 A ratings).
IEC Standards:
IEC 60044-1: Specifications for CTs, defining accuracy classes, transient performance, and testing methods.
IEC 61850: Digital substation standards for CTs in merged unit (MU) configurations for digital protection systems.
IEEE Standards:
IEEE C57.13: Requirements for CTs in power systems, including ratings, tests, and application guidelines.
Digital CTs (Electronic CTs):
Use optical fiber or low-power electromagnetic sensors to replace traditional CTs, reducing size, weight, and magnetic saturation risks (e.g., IEC 60044-8 compliant).
Intelligent Electronic Devices (IEDs) Integration:
Condition Monitoring of CTs:
CT configuration in substation relay protection systems must balance technical requirements (accuracy, reliability, transient performance) with practical constraints (cost, space, maintainability). Key principles include strategic placement for protection zoning, appropriate rating for fault current withstand, redundancy for reliability, and compliance with international standards. As power systems evolve toward digitization and intelligence, CT configurations are adapting to support advanced protection schemes and smart grid operations.