News

Burden Ratings in Potential Transformers: A Technical Overview

Potential transformers (PTs), also known as voltage transformers (VTs), are critical components in power systems, responsible for stepping down high voltages to measurable levels for metering, protection, and control. A key specification that determines their performance and reliability is the burden rating—a parameter that defines the maximum load a PT can handle while maintaining accuracy and stability. Understanding burden ratings is essential for proper PT selection, system design, and troubleshooting, as an incorrectly sized burden can lead to measurement errors, protection failures, or equipment damage. This article provides a technical overview of burden ratings in potential transformers, covering their definition, significance, influencing factors, and practical applications.
1. Defining Burden Rating in Potential Transformers
The burden rating of a potential transformer refers to the maximum apparent power (in volt-amperes, VA) that the PT can supply to its secondary circuit without exceeding specified accuracy limits. It represents the total load imposed by connected devices such as meters, relays, indicators, and wiring, measured at the PT’s secondary terminals.
Burden is typically expressed in two forms:
  • Rated Burden: The maximum VA load at which the PT meets its accuracy class (e.g., 0.5 or 1.0) under rated voltage and frequency conditions.

  • Maximum Burden: The highest VA load the PT can tolerate without overheating or mechanical stress, even if accuracy is compromised. This is often 150–200% of the rated burden.

For example, a PT with a rated burden of 200 VA can reliably power devices totaling 200 VA (e.g., a 100 VA meter + 50 VA relay + 50 VA wiring loss) while maintaining Class 0.5 accuracy. Exceeding this load may cause voltage drops in the secondary circuit, distorting measurements.
Burden is also sometimes specified in terms of impedance (ohms), derived from the relationship:
Burden (VA) = (Secondary Voltage)² / Impedance (Ω)
For standard PTs with a secondary voltage of 110 V, a 200 VA burden corresponds to approximately 60.5 Ω (110² / 200).
2. Significance of Burden Ratings in Power Systems
Burden ratings directly impact the performance and reliability of PTs and the systems they support. Their importance stems from several critical roles:
2.1 Accuracy Maintenance
Potential transformers are designed to maintain precise voltage ratios within defined error limits (e.g., ±0.5% for Class 0.5). When the connected burden exceeds the rated value, the secondary voltage drops due to internal impedance, causing the transformation ratio to deviate from its ideal value. This leads to:
  • Metering Errors: Incorrect energy measurements, resulting in billing inaccuracies for utilities or industrial users.

  • Protection Miscalculations: Relays relying on PT data may underreact or overreact to faults, either failing to isolate issues or triggering unnecessary outages.

2.2 Thermal Stability
Excessive burden increases current flow in the PT’s secondary windings, raising copper losses (I²R) and generating heat. Over time, sustained overloading can:
  • Degrade insulation materials, shortening the PT’s lifespan.

  • Cause thermal runaway in extreme cases, leading to insulation breakdown or fire.

2.3 Voltage Regulation
The secondary voltage of a PT must remain stable under varying load conditions to ensure consistent operation of connected devices. A burden beyond the rated limit causes voltage sag, which can:
  • Disrupt sensitive electronics in metering or control systems.

  • Reduce the accuracy of protective relays, which depend on stable voltage references.

2.4 Compliance with Standards
International standards such as IEC 60044-2 and IEEE C57.13 define burden rating requirements for PTs, specifying maximum VA loads for different accuracy classes. Compliance with these standards ensures interoperability and reliability across power system components.
3. Factors Influencing Burden Ratings
The burden rating of a potential transformer is not a fixed value but depends on several design and operational factors. Manufacturers must account for these variables when specifying ratings, while system designers must consider them during installation.
3.1 PT Design Characteristics
  • Core Material and Geometry: High-permeability core materials (e.g., grain-oriented silicon steel) reduce magnetic losses, allowing the PT to handle higher burdens without overheating. Larger core cross-sections also improve heat dissipation, increasing burden capacity.

  • Winding Conductivity: Secondary windings made from high-purity copper (low resistance) minimize I²R losses, enabling higher VA ratings compared to windings with higher resistance (e.g., aluminum).

  • Insulation Class: PTs with higher insulation classes (e.g., Class F, 155°C) can tolerate more heat, supporting higher burden ratings than those with lower classes (e.g., Class B, 130°C).

  • Cooling Mechanism: Oil-immersed PTs typically have higher burden ratings than dry-type PTs due to better heat transfer through convection in oil.

3.2 Operational Conditions
  • Frequency: Burden ratings are specified for a nominal frequency (e.g., 50 Hz or 60 Hz). Operation at off-nominal frequencies can increase losses, reducing the effective burden capacity. For example, a 50 Hz PT operated at 60 Hz may experience higher eddy current losses, lowering its maximum safe burden.

  • Ambient Temperature: High ambient temperatures (e.g., in outdoor substations) reduce the PT’s ability to dissipate heat, effectively lowering its burden rating. Manufacturers often provide derating curves showing reduced burden capacity at temperatures above 30°C.

  • Voltage Variation: Overvoltage conditions (e.g., 110% of rated voltage) increase core losses, reducing the available capacity for burden. Conversely, undervoltage may lower losses but can cause accuracy issues in connected devices.

3.3 Secondary Circuit Components
The total burden on a PT is the sum of loads from all connected devices and wiring:
  • Active Devices: Meters, relays, and control systems draw real power (watts), contributing to resistive losses.

  • Reactive Components: Inductive loads (e.g., relay coils) or capacitive loads (e.g., cable capacitance) introduce reactive power (vars), increasing the apparent power (VA) burden.

  • Wiring Losses: Secondary cables have resistance and inductance, which add to the total burden. Longer cables or smaller gauge wires increase this contribution significantly. For example, 100 feet of 18 AWG wire adds approximately 2.5 Ω, equivalent to ~5 VA at 110 V (110² / 2.5 = 4840 VA, but actual loss depends on current).

4. Burden Calculation and Selection
Properly calculating the total burden on a PT is critical for ensuring accuracy and reliability. The process involves summing the contributions from all secondary circuit components and verifying that the total does not exceed the PT’s rated burden.
4.1 Step-by-Step Burden Calculation
  1. List Connected Devices: Identify all devices connected to the PT’s secondary, including meters, relays, transducers, and indicators.

  1. Determine Individual Burdens: Check manufacturer datasheets for each device’s VA rating at nominal voltage (e.g., a digital meter may require 5 VA, a protective relay 10 VA).

  1. Account for Wiring Losses: Calculate the burden from secondary wiring using the formula:

Wiring Burden (VA) = (Secondary Voltage)² / Wiring Impedance (Ω)
Wiring impedance depends on cable length, gauge, and material (copper vs. aluminum). For example, 50 meters of 2.5 mm² copper cable has an impedance of ~0.35 Ω, contributing ~34 VA (110² / 0.35) at 110 V.
  1. Sum Total Burden: Add the burdens of all devices and wiring to get the total load.

  1. Compare to PT Rating: Ensure the total burden is ≤ the PT’s rated burden. If exceeding, either reduce the load (e.g., remove non-critical devices) or select a PT with a higher rating.

4.2 Example Calculation
For a PT supplying:
  • 1 digital energy meter (5 VA)

  • 2 protective relays (10 VA each)

  • 1 indicator light (2 VA)

  • 30 meters of 1.5 mm² copper wiring (impedance = 0.4 Ω, contributing 30.25 VA)

Total Burden = 5 + (2×10) + 2 + 30.25 = 57.25 VA
A PT with a rated burden of 60 VA or higher would be suitable.
4.3 Accuracy Class and Burden
PT accuracy classes (e.g., 0.1, 0.2, 0.5, 1.0) are defined for specific burden ranges. For example, a Class 0.5 PT may maintain accuracy from 25% to 100% of its rated burden. Operating below 25% of the rated burden can also cause errors due to core saturation effects. Thus, the total burden should ideally fall within 50–100% of the rated value for optimal performance.
5. Burden Rating Standards and Specifications
International standards establish uniform guidelines for burden ratings, ensuring consistency across manufacturers and applications. The two most influential standards are:
5.1 IEC 60044-2 (International Electrotechnical Commission)
IEC 60044-2 specifies burden ratings for voltage transformers, defining:
  • Standard Burden Values: Common rated burdens include 10 VA, 20 VA, 50 VA, 100 VA, 200 VA, 500 VA, and 1000 VA.

  • Accuracy Classes: For each class (e.g., 0.1, 0.2, 0.5), the standard defines maximum ratio and phase errors at rated burden and 25% of rated burden.

  • Temperature Rise Limits: Maximum allowable temperature rises (e.g., 60 K for Class A insulation) when operating at rated burden, ensuring thermal safety.

5.2 IEEE C57.13 (Institute of Electrical and Electronics Engineers)
IEEE C57.13 is widely used in North America, with similar provisions to IEC 60044-2 but with some differences:
  • Burden Designations: Burdens are often designated by letters (e.g., B-0.1, B-0.2) corresponding to VA values (e.g., 10 VA, 20 VA).

  • Voltage Ratings: The standard includes specific burden requirements for PTs used in distribution (e.g., 12.47 kV) and transmission (e.g., 115 kV) systems.

  • Short-Time Overload Capability: Specifies maximum burdens for short durations (e.g., 200% of rated burden for 30 minutes) without damage.

5.3 Manufacturer-Specific Ratings
Manufacturers may also provide custom burden ratings for specialized applications, such as PTs used in renewable energy systems or harsh environments. These ratings often include derating factors for high temperatures, altitude, or vibration.
6. Practical Challenges and Mitigation Strategies
Despite careful calculation, burden-related issues can arise in power systems, leading to PT underperformance. Recognizing these challenges and implementing mitigation strategies is key to maintaining reliability.
6.1 Overburdening
  • Challenge: Adding new devices to an existing secondary circuit (e.g., retrofitting smart meters) can exceed the PT’s rated burden, causing accuracy degradation or overheating.

  • Mitigation:

  • Upgrade the PT: Replace the existing PT with one of higher burden rating.

  • Reduce Load: Remove non-essential devices or replace high-VA devices with low-power alternatives (e.g., solid-state relays instead of electromechanical ones).

  • Use a Burden Resistor: Install a resistor in parallel with the secondary circuit to 分流 excess current, though this may reduce accuracy.

6.2 Voltage Drop in Secondary Wiring
  • Challenge: Long secondary cables (e.g., in large substations) introduce significant impedance, increasing the total burden and causing voltage sag.

  • Mitigation:

  • Use Larger Gauge Cable: Thicker wires reduce resistance, lowering wiring burden. For example, upgrading from 18 AWG to 14 AWG cable reduces resistance by ~60% for the same length.

  • Shorten Cable Length: Route cables directly to minimize distance between the PT and connected devices.

  • Install a Voltage Regulator: A small transformer or booster can compensate for voltage drop in long cables.

6.3 Reactive Burden Issues
  • Challenge: Inductive loads (e.g., relay coils) increase the reactive component of the burden, raising apparent power (VA) without increasing real power (watts). This can push the total burden above the rated limit even if active power is low.

  • Mitigation:

  • Add Power Factor Correction Capacitors: Connecting capacitors in parallel with inductive loads reduces reactive power, lowering the total VA burden.

  • Use Low-Reactance Devices: Replace inductive relays with solid-state versions, which have minimal reactive components.

6.4 Temperature-Related Derating
  • Challenge: In hot climates (e.g., desert regions) or enclosed spaces, high ambient temperatures reduce the PT’s effective burden rating, increasing the risk of overheating.

  • Mitigation:

  • Select a Higher Insulation Class: PTs with Class H insulation (180°C) can operate at higher temperatures than Class B (130°C), maintaining burden capacity in heat.

  • Improve Cooling: Install fans or heat sinks in enclosures to reduce ambient temperature around the PT.

  • Derate the PT: Reduce the maximum allowable burden based on manufacturer-provided derating curves (e.g., 80% of rated burden at 40°C).

7. Applications and Burden Rating Considerations
Burden rating requirements vary across different power system applications, depending on the number and type of connected devices. Understanding these variations is critical for selecting appropriate PTs.
7.1 Utility Distribution Systems
In distribution substations (e.g., 11 kV–33 kV), PTs typically supply:
  • Revenue meters (5–20 VA)

  • Overvoltage/undervoltage relays (10–30 VA)

  • SCADA transducers (5–15 VA)

Total burdens range from 30–100 VA, requiring PTs with rated burdens of 50–200 VA. Accuracy is critical here to ensure correct billing and reliable protection.
7.2 Industrial Power Systems
Industrial PTs may supply:
  • Process control systems (20–50 VA)

  • Motor protection relays (15–40 VA)

  • Energy management systems (10–25 VA)

Total burdens are often higher (100–500 VA) due to more numerous devices, requiring PTs with rated burdens of 200–1000 VA. Robust designs are needed to handle industrial EMI and temperature fluctuations.
7.3 Renewable Energy Systems
In solar or wind farms, PTs monitor voltage at inverter outputs and grid connection points, supplying:
  • Inverter control systems (10–30 VA)

  • Grid synchronization relays (20–50 VA)

  • Data loggers (5–15 VA)

Burdens are typically 50–200 VA, but PTs must also handle voltage fluctuations from variable generation, requiring wide burden ranges (25–120% of rated).
7.4 Rural Electrification Projects
In rural grids, PTs often supply basic metering and protection devices with low burdens (10–50 VA). However, long wiring runs (due to dispersed loads) can significantly increase total burden, requiring PTs with higher ratings (e.g., 100 VA) to account for wiring losses.
8. Conclusion
Burden ratings are a fundamental aspect of potential transformer performance, governing accuracy, thermal stability, and reliability in power systems. By defining the maximum load a PT can handle while maintaining specifications, burden ratings guide proper selection, installation, and maintenance. System designers must carefully calculate total burdens from connected devices and wiring, ensuring they align with PT ratings and standards such as IEC 60044-2 and IEEE C57.13.
Challenges like overburdening, voltage drop, and temperature effects can be mitigated through careful planning—whether by upgrading PTs, optimizing wiring, or adding power factor correction. As power systems evolve with smart grid technologies and renewable integration, understanding burden ratings will remain critical for ensuring the integrity of voltage measurement and protection systems.
In summary, burden ratings are not just technical specifications but essential safeguards that ensure potential transformers deliver accurate, reliable performance across diverse applications—from urban substations to remote rural grids.


avatar
XUJIA

I graduated from the University of Electronic Science and Technology, majoring in electric power engineering, proficient in high-voltage and low-voltage power transmission and transformation, smart grid and new energy grid-connected technology applications. With twenty years of experience in the electric power industry, I have rich experience in electric power design and construction inspection, and welcome technical discussions.

Share This Article
Whatsapp
Email
Message