News

Analysis of Selection Criteria for Rated Secondary Current of Current Transformers

1. Introduction

Current transformers (CTs) are critical components in power systems, responsible for transforming high primary currents into manageable secondary currents for measurement, protection, and control purposes. The selection of the rated secondary current is a foundational decision that directly impacts the accuracy, safety, and efficiency of the entire system. This article provides a comprehensive analysis of the key criteria for choosing the rated secondary current of CTs, exploring technical, operational, and practical considerations. By understanding these criteria, engineers and system designers can ensure optimal performance of CTs in diverse power system applications.

2. Fundamentals of Rated Secondary Current

The rated secondary current of a CT is the standard current value at which the transformer is designed to operate under nominal conditions. It serves as the reference for calibrating connected devices such as ammeters, relays, and energy meters. Internationally recognized standards, such as IEC 61869 and ANSI/IEEE C57.13, define common rated secondary currents, with 5 A and 1 A being the most prevalent in industrial and utility systems. Other values, such as 0.5 A or 10 A, may be specified for specialized applications, but they are far less common.


The primary function of standardizing secondary currents is to ensure compatibility between CTs and downstream equipment. For example, a relay designed for a 5 A input will not operate correctly if connected to a CT with a 1 A secondary output, and vice versa. Thus, the rated secondary current acts as a critical interface parameter in power system design.

3. Key Selection Criteria

3.1 Compatibility with Connected Equipment

The most fundamental criterion for selecting the rated secondary current is compatibility with the input requirements of connected devices. Protective relays, measuring instruments, and data acquisition systems are all designed to operate with specific secondary current ratings.


  • Protective Relays: Modern digital relays often support multiple input ratings (e.g., 1 A or 5 A) via configuration, but electromechanical relays are typically fixed to one rating. Using a mismatched CT can lead to undercurrent or overcurrent conditions in the relay, resulting in incorrect tripping or failure to operate during faults.

  • Meters and Indicators: Analog meters (e.g., moving-coil ammeters) are calibrated for a specific secondary current. A 5 A meter connected to a 1 A CT will display only 20% of the actual current, leading to misleading readings.

  • Data Acquisition Systems: Current transducers and analog-to-digital converters (ADCs) in SCADA systems require the secondary current to fall within their input range for accurate digitization. Overloading these components can cause saturation or damage.


Engineers must therefore review the specifications of all downstream equipment to ensure the CT’s secondary rating aligns with their input requirements.

3.2 Power Loss and Cable Efficiency

The rated secondary current significantly influences power losses in the secondary circuit, particularly in long cable runs. Power loss in the secondary loop is governed by Joule’s law: P=I2R, where I is the secondary current and R is the total resistance of the cable and connections.


  • 5 A Systems: Higher secondary currents result in greater power losses. For example, a 5 A CT with a 100 m cable (copper, 4 mm², resistance ≈ 5 Ω/km) will dissipate 52×(0.1×5)=12.5 W. This can lead to excessive heating in enclosed cabinets, requiring larger cable sizes or additional cooling.

  • 1 A Systems: Lower secondary currents reduce losses. The same 100 m cable with a 1 A CT dissipates 12×0.5=0.5 W, minimizing heat generation and allowing the use of smaller, more cost-effective cables.


In applications with long cable runs (e.g., substation to control room distances exceeding 50 m), 1 A CTs are often preferred to reduce energy waste and cable costs. Conversely, in compact systems with short cable lengths (e.g., switchgear panels), 5 A CTs may be more practical due to their widespread availability.

3.3 Accuracy Requirements

CT accuracy is defined by its accuracy class, which specifies the maximum permissible error at rated current and burden. The rated secondary current affects accuracy because it influences the CT’s operating point on its magnetization curve.


  • Low Burden Applications: For measuring circuits with low burdens (e.g., < 5 VA), 1 A CTs often exhibit better accuracy. Their lower current reduces voltage drop across the burden, keeping the CT closer to its optimal operating range.

  • High Burden Applications: Protective circuits with higher burdens (e.g., 10–30 VA) may benefit from 5 A CTs. The higher secondary voltage (due to V=I×Z, where Z is the burden impedance) helps maintain linearity, especially during fault conditions.


For example, a class 0.2 CT (for revenue metering) with a 5 A secondary may achieve ±0.2% accuracy at 100% rated current, but a 1 A CT of the same class might perform better at lower burdens. Engineers must match the secondary current to the accuracy class and burden to ensure compliance with regulatory standards (e.g., IEC 61869-2 for measuring CTs).

3.4 Fault Current Handling

During short-circuit conditions, CTs must accurately transform high primary fault currents to enable protective relays to operate correctly. The rated secondary current influences the CT’s ability to handle these transient events.


  • Saturation Risk: CTs with lower secondary currents (e.g., 1 A) may saturate more easily under fault conditions if the burden is not properly matched. Saturation distorts the secondary current waveform, delaying or invalidating relay operation.

  • Relay Sensitivity: 1 A CTs produce smaller fault currents in the secondary circuit, requiring relays to have higher sensitivity to detect low-level faults. Modern digital relays can compensate for this, but older electromechanical relays may struggle.

  • Thermal Rating: The secondary winding must withstand thermal stresses during faults. 5 A CTs typically have thicker secondary conductors, offering better thermal endurance in high-fault scenarios.


In systems with high fault levels (e.g., transmission networks with fault currents exceeding 50 kA), 5 A CTs are often favored for their robust fault handling, while 1 A CTs may be used in distribution systems with lower fault currents (e.g., < 20 kA) and advanced relays.

3.5 System Voltage and Scalability

The voltage level of the power system indirectly influences the choice of secondary current.


  • High-Voltage (HV) Systems: HV substations often use 1 A CTs due to long cable runs between the CTs (mounted on HV bushings) and control rooms. The reduced power loss and cable cost outweigh the need for higher current levels.

  • Low-Voltage (LV) Systems: LV switchgear and industrial plants typically use 5 A CTs. Shorter cable runs minimize losses, and 5 A equipment is more readily available and cost-effective for small-scale applications.


Scalability is another consideration. In expanding systems, using 1 A CTs can future-proof the design, as adding more devices to the secondary circuit increases the burden, and 1 A systems are more tolerant of higher impedances.

3.6 Industry Standards and Regional Practices

Regional preferences and industry standards play a significant role in secondary current selection.


  • IEC Regions: Europe, Asia, and most of the world follow IEC standards, where both 1 A and 5 A are common. 1 A is prevalent in HV systems, while 5 A dominates in LV and industrial applications.

  • ANSI Regions: North America primarily uses 5 A CTs, reflecting historical practices and the prevalence of ANSI/IEEE standards that emphasize 5 A for most applications.

  • Specialized Sectors: Renewable energy systems (e.g., wind farms) often adopt 1 A CTs to minimize losses in long cable runs from turbines to control centers. Railway electrification systems may use 0.5 A CTs for low-power, high-precision measurements.


Adhering to regional standards ensures interoperability and simplifies procurement, as local suppliers are more likely to stock CTs with the dominant secondary rating.

3.7 Cost Considerations

The total cost of ownership includes not only the CT itself but also cables, connectors, and associated equipment.


  • CT Cost: 5 A CTs are generally cheaper than 1 A CTs of equivalent rating due to higher production volumes and simpler design (thicker secondary windings).

  • Cable Cost: For long distances, 1 A systems offer significant savings. A 100 m run using 4 mm² cable costs approximately 30% less than the 10 mm² cable required for a 5 A system to achieve the same loss levels.

  • Equipment Cost: 5 A relays and meters are often more affordable and widely available, especially in regions where they are standard.


A cost-benefit analysis must balance these factors. For example, in a large substation with 200 m cable runs, the savings from using 1 A CTs and smaller cables typically outweigh the higher initial CT cost.

4. Comparative Analysis: 5 A vs. 1 A Secondary Currents

To summarize the key differences, Table 1 compares 5 A and 1 A secondary currents across critical parameters:


Parameter5 A Secondary Current1 A Secondary Current
Power LossHigher (I²R)Lower (I²R)
Cable SizeLarger (to minimize resistance)Smaller (reduced resistance requirement)
Accuracy at Low BurdenLowerHigher
Fault HandlingBetter thermal enduranceRequires higher relay sensitivity
AvailabilityWidespread (especially in ANSI regions)Common in IEC regions, HV systems
Cost (CT)LowerHigher
Cost (Cables)Higher (for long runs)Lower (for long runs)


Table 1: Comparison of 5 A and 1 A Secondary Currents

5. Special Applications and Edge Cases

In some scenarios, non-standard secondary currents or hybrid approaches may be required:


  • Microgrids: Small-scale microgrids with limited fault currents may use 0.5 A CTs to enhance measurement accuracy in low-current conditions.

  • DC Systems: While CTs are primarily for AC, some DC current transducers use 1 A outputs to interface with standard AC equipment via rectification.

  • Mixed Systems: In retrofits, adapters (e.g., 5 A to 1 A current transformers) can bridge incompatible ratings, though this introduces additional losses and potential inaccuracies.

6. Selection Process Flowchart

A structured approach to selecting the rated secondary current involves the following steps:


  1. Identify the input requirements of all connected devices (relays, meters, etc.).

  2. Calculate the secondary circuit length and required burden.

  3. Evaluate power loss and cable size constraints.

  4. Assess accuracy class and fault current handling needs.

  5. Consider regional standards and equipment availability.

  6. Perform a cost-benefit analysis of 5 A vs. 1 A systems.

  7. Validate the selection with system simulations (e.g., using PSCAD or ETAP) to ensure compliance with performance targets.

7. Conclusion

The selection of a CT’s rated secondary current is a multifaceted decision that impacts system accuracy, efficiency, and cost. While 5 A remains dominant in LV systems and regions following ANSI standards, 1 A is preferred for HV applications, long cable runs, and IEC-compliant systems due to its lower losses and improved efficiency. By systematically evaluating compatibility, power loss, accuracy, fault handling, and cost, engineers can select the optimal rating to ensure reliable and economical operation of power systems.


Adherence to international standards and regional practices further ensures interoperability, while periodic reviews of system performance (e.g., during maintenance) can identify opportunities to upgrade or modify CT ratings as operational needs evolve. Ultimately, the right choice balances technical requirements with practical and economic considerations, laying the foundation for a robust and efficient power system.


avatar
XUJIA

I graduated from the University of Electronic Science and Technology, majoring in electric power engineering, proficient in high-voltage and low-voltage power transmission and transformation, smart grid and new energy grid-connected technology applications. With twenty years of experience in the electric power industry, I have rich experience in electric power design and construction inspection, and welcome technical discussions.

Share This Article
Whatsapp
Email
Message