Current transformers (CTs) are critical components in power systems, serving two primary functions: measurement (providing accurate current signals for metering) and protection (triggering protective relays during faults). During short-circuit faults, CTs are subjected to extreme electrical and mechanical stresses—specifically, high currents that generate excessive heat (thermal stress) and intense electromagnetic forces (mechanical stress). To ensure CTs survive such events without permanent damage, two key parameters are defined: rated short-time thermal current and dynamic stability current. These parameters are fundamental to CT design, selection, and validation, directly impacting the reliability and safety of power systems. This analysis explores their definitions, underlying principles, standards, calculations, and practical applications.
The rated short-time thermal current (often denoted as Ith) is the maximum rms current that a CT’s windings can withstand for a specified duration (typically 1s, 2s, or 3s) without exceeding permissible temperature limits. This parameter ensures the CT’s insulation and conductor materials do not degrade due to excessive heat generated during short circuits.
Short-circuit currents, which can be 10–100 times higher than rated current, induce significant heat in CT windings via Joule-Lenz law: Q=I2Rt, where Q is heat energy (in joules), I is current (rms), R is winding resistance, and t is duration (in seconds). This heat raises the winding temperature; exceeding the insulation’s maximum allowable temperature (e.g., 250°C for Class B insulation, 180°C for Class F) causes irreversible damage (e.g., insulation cracking, conductor annealing).
The thermal capability of a CT is better characterized by the I2t withstand value (the product of the square of the rated short-time current and the duration). This value represents the total thermal energy the CT can absorb without failure. For example, a CT rated at 31.5kA for 1s has an I2t value of 31.52×1=992.25kA2s.
When selecting a CT, its I2t withstand value must exceed the I2t of the actual short-circuit current in the system. The system’s short-circuit I2t depends on the fault current magnitude and the time it takes for protective devices (e.g., circuit breakers) to clear the fault.
International standards (e.g., IEC 61869-2, ANSI C57.13) specify standard durations for Ith:
1 second: Most common for medium-voltage (MV) and high-voltage (HV) systems, aligning with typical breaker clearing times.
2 seconds or 3 seconds: Used in systems where faults may persist longer (e.g., remote grids with slower protection).
Standards also define temperature limits: for example, IEC 61869-2 requires that after the short-time test, winding temperatures must not exceed 250°C (for Class B insulation) or 180°C (for Class F), measured by resistance methods or thermocouples.
To determine Ith, manufacturers consider:
Winding material (copper or aluminum) and cross-sectional area (affecting resistance R).
Insulation class (defining maximum temperature).
Heat dissipation (via conduction, convection, or radiation, though negligible during short durations).
The formula for Ith is derived from thermal energy balance:Ith=R⋅tC⋅ΔT
Where:
C = thermal capacity of the winding (J/°C).
ΔT = allowable temperature rise (°C).
R = winding resistance at operating temperature (Ω).
t = duration (s).
Validation involves short-time thermal tests: CTs are subjected to Ith for the specified duration, and post-test inspections confirm no insulation breakdown or conductor damage.
The dynamic stability current (denoted as Idyn) is the maximum peak current a CT can withstand without mechanical damage (e.g., winding deformation, insulation displacement) due to electromagnetic forces generated during short circuits. Unlike Ith, it focuses on mechanical stress rather than thermal effects.
Short-circuit currents produce intense magnetic fields, creating electromagnetic forces between parallel current-carrying conductors (Ampère’s law). For CTs, these forces act between primary and secondary windings, as well as between turns within a winding. The force magnitude is proportional to the square of the current and inversely proportional to the distance between conductors:F∝dI2
Where d is the distance between conductors.
During symmetric short circuits, the fault current waveform has a peak value (due to AC asymmetry) equal to 22Isc,rms≈2.828Isc,rms, where Isc,rms is the rms short-circuit current. For asymmetric faults (e.g., single-line-to-ground), the peak can be higher (up to 2.55Isc,rms for 50Hz systems, as defined by IEC). This peak current induces the maximum mechanical force, making Idyn a peak value rather than an rms value.
Idyn is often specified as a multiple of Ith. For symmetric faults, the ratio is typically 2.55 (derived from 2×1.8, where 1.8 accounts for DC offset in asymmetric faults). For example, a CT with Ith=31.5kA (rms, 1s) may have Idyn=31.5×2.55≈80kA (peak).
To withstand Idyn, CTs require robust mechanical design:
Winding bracing: Reinforcements (e.g., epoxy resin, glass fiber) prevent winding displacement.
Conductor rigidity: Thick, rigid conductors resist bending under force.
Insulation spacing: Adequate distance between windings reduces force intensity while maintaining insulation integrity.
Standards like IEC 61869-2 and ANSI C57.13 define Idyn test procedures: CTs are subjected to a peak current equal to Idyn (simulating the first half-cycle of a short circuit). Post-test checks include:
Visual inspection for winding deformation or insulation damage.
Electrical tests (e.g., turns ratio, insulation resistance) to confirm no performance degradation.
Despite their differences, Ith and Idyn are complementary: a CT must satisfy both to survive short circuits. For example, a CT with high Ith but low Idyn may avoid thermal damage but fail mechanically; conversely, a CT with high Idyn but low Ith may melt due to prolonged heat.
Selecting a CT requires matching Ith and Idyn to the system’s short-circuit characteristics:
Determine the maximum rms short-circuit current (Isc,rms) at the CT location (using software like ETAP or PSCAD).
Estimate the fault clearing time (tclear) (e.g., 0.5s for fast-acting breakers).
Compute the system’s I2t value: Isc,rms2×tclear.
Calculate the peak short-circuit current: Isc,peak=k×Isc,rms, where k≈2.55 (asymmetric faults).
Ith: Choose a CT with Ith2×trated≥Isc,rms2×tclear. For example, if Isc,rms=40kA and tclear=0.5s, the system I2t=402×0.5=800kA2s. A CT with Ith=50kA (1s) has 502×1=2500kA2s, which is sufficient.
Idyn: Ensure Idyn≥Isc,peak. For Isc,peak=40×2.55=102kA, select a CT with Idyn≥125kA (a common standard value).
IEC 61869-2: Specifies requirements for CTs, including Ith (1s, 2s) and Idyn (peak, 2.55×Ith for symmetric faults).
ANSI C57.13: Defines thermal ratings (e.g., 10kA for 30s) and mechanical ratings (e.g., 200kA peak) for distribution and power CTs.
IEEE C57.13.1: Provides test procedures for verifying Ith and Idyn, including temperature rise and mechanical stress tests.
Rated short-time thermal current and dynamic stability current are critical metrics ensuring current transformers survive short-circuit faults. Ith safeguards against thermal degradation, while Idyn prevents mechanical failure. Proper selection, based on system short-circuit calculations and adherence to standards, is essential for maintaining power system reliability. Engineers must balance both parameters to avoid under-sizing (risk of CT failure) or over-sizing (increased cost). As power systems evolve with higher fault levels (e.g., due to renewable integration), these parameters will remain central to CT design and application.