Monitoring and Metering: Providing real-time current data for energy management systems (EMS), power usage effectiveness (PUE) calculations, and load balancing. Accuracy at both low and high load levels is critical here.
Protection: Triggering circuit breakers or UPS shutdown mechanisms during overloads, short circuits, or ground faults to prevent equipment damage. Fast response and saturation immunity are key for protective CTs.
Control and Regulation: Enabling UPS inverters to maintain stable output voltage/current by feeding back measured values to control loops. This requires low phase shift and wide frequency response.
Selection Criteria:
The primary rated current must exceed the maximum expected current in the UPS circuit, including transient spikes (e.g., 125% of UPS rated current to account for overloads). For example, a 200kVA UPS (400V, 3-phase) has a rated current of ~288A; a CT with a 400A/5A ratio provides a safety margin.
Secondary current (1A vs. 5A) depends on cable length and burden. 1A is preferred for long cable runs (>30m) to minimize power loss (P=I2R), while 5A is more robust against noise in short runs.
Avoid undersizing: A CT with a ratio too small (e.g., 300A/5A for a 288A UPS) risks saturation during transients, leading to measurement errors or protection failures.
For energy metering and PUE tracking, Class 0.2 (±0.2% ratio error at rated current) ensures precise kWh calculations.
At low loads (e.g., 10% of rated current), accuracy degrades; select CTs with guaranteed performance down to 5% load (e.g., Class 0.5S, where “S” denotes extended range).
Protection CTs prioritize linearity during fault currents (up to 20–100x rated current) over absolute accuracy. Class 5P allows a 5% ratio error at 10x rated current (10P for 10% error).
For fast-acting UPS protection (e.g., short-circuit clearing in <10ms), transient-rated CTs (TPY/TPZ) are preferred. They minimize saturation under DC offset conditions (common in rectifier faults), ensuring relays operate reliably.
Calculation: Burden = Is2×(Rcable+Rdevice), where Rcable depends on length and gauge (e.g., 10m of 1.5mm² copper has ~0.12Ω resistance).
Selection: Choose a CT with a rated burden (e.g., 5VA, 10VA) exceeding the calculated value. For example, a 5A CT with 10m cable and a 0.5Ω relay has a burden of 52×(0.12+0.5)=15.5VA; select a 20VA CT.
High-burden risks: Exceeding rated burden increases ratio error and may cause saturation.
ALF (Accuracy Limit Factor): For protection CTs, ALF is the ratio of the maximum primary current (at which accuracy is maintained) to the rated primary current. A 5P10 CT with ALF=10 can handle 10x rated current with ≤5% error.
Knee Point Voltage (Vk): The voltage at which the core begins to saturate. For stable operation, Vk≥2×Is×Zburden (where Zburden is total secondary impedance).
Flat frequency response from 50Hz/60Hz up to at least 2kHz (to capture 30th harmonic in 60Hz systems).
Low phase shift across frequencies to ensure accurate power factor measurements.
Form Factor: Split-core CTs (clamp-on design) simplify retrofitting onto existing UPS cables without disconnecting power, ideal for upgrades. Solid-core CTs offer higher accuracy but require cable disconnection during installation.
Mounting: DIN-rail or panel-mount options save space; ensure compatibility with UPS enclosure dimensions (e.g., depth ≤100mm for rack-mounted UPS).
Cable Compatibility: The CT’s window size must accommodate the primary cable (e.g., 50mm diameter for 400A cables).
Operating Temperature Range: Select CTs rated for -25°C to +70°C (wider than standard industrial CTs) to withstand transient temperature spikes.
Insulation Class: Class F (155°C) or H (180°C) insulation ensures long-term reliability, as higher temperatures accelerate insulation degradation.
Humidity Resistance: IP20 or higher ingress protection (with sealed enclosures) prevents moisture damage in humid environments.
Immunity: CTs must comply with IEC 61000-6-2 (industrial environment) for resistance to radiated (30MHz–1GHz) and conducted (0.15–80MHz) EMI.
Emissions: Low EMI emissions to avoid interfering with UPS control circuits or sensitive monitoring equipment.
Shielding: Coaxial secondary cables or shielded CT housings reduce noise coupling (see Section 3 of previous analysis on shielding).
CT Requirements:
High accuracy at low loads (since UPS operates at 30–70% load in normal mode).
Wide frequency response to measure input harmonics (for compliance with IEEE 519).
Protection CTs with fast response (≤5ms) to detect inverter faults.
CT Requirements:
Small form factor to fit within modules.
Low inter-module interference (via shielding) to avoid cross-talk between CTs.
High linearity for accurate current sharing between modules (±1% error).
CT Requirements:
Frequency response up to 10kHz to capture switching harmonics.
Low core losses at high frequencies (use ferrite or nanocrystalline cores instead of silicon steel).
Special Considerations:
DC-compatible CTs (e.g., Hall-effect sensors) or AC-coupled CTs with rectification for pulsating DC.
High current rating (battery discharge currents can exceed 10x UPS rated current).
IEC 61869-2: Specifies performance for measuring and protective CTs, including accuracy classes and thermal ratings.
ANSI C57.13: Defines standards for instrument transformers in North American markets, with emphasis on burden and saturation.
UL 1414: Safety standard for current transformers, ensuring insulation integrity and fire resistance.
TIA-942: Data center standards (e.g., Tier 4) requiring CTs to support 99.995% uptime, mandating high reliability and redundancy.
Premium CTs (e.g., Class 0.1, TPY, wide frequency response) offer superior performance but cost 2–3x more than standard models. They are justified for critical applications (e.g., Tier 4 data centers, mission-critical UPS).
Economical CTs (e.g., Class 0.5, 5P10) suffice for non-critical systems (e.g., backup UPS for office areas) but may require more frequent calibration.
Lifecycle Costs: Cheaper CTs with poor thermal tolerance may fail prematurely in high-density environments, increasing replacement and downtime costs.
Current Calculation: UPS rated current = 1200kVA / (√3 × 400V) ≈ 1732A. Select primary current = 2000A (25% margin).
Accuracy Needs:
Input/output monitoring: Class 0.2S (to measure 5–100% load accurately).
Protection: TPY class (transient immunity) with ALF=30 (handles 30×2000A=60kA faults).
Burden Calculation: 5A secondary, 15m cable (0.2Ω), and 0.8Ω relay → burden = 5²×(0.2+0.8) = 25VA. Select 30VA CT.
Environmental: 40°C max temperature → Class H insulation, -25°C to +70°C range.
Form Factor: Split-core DIN-rail CTs for easy installation in modular bays.
I graduated from the University of Electronic Science and Technology, majoring in electric power engineering, proficient in high-voltage and low-voltage power transmission and transformation, smart grid and new energy grid-connected technology applications. With twenty years of experience in the electric power industry, I have rich experience in electric power design and construction inspection, and welcome technical discussions.